[36802] Artykuł: New reliability coefficients of MV/LV transformer/distribution substation and its componentsCzasopismo: International Journal of Electrical Power & Energy Systems Tom: 43, Zeszyt: 1, Strony: 992-995ISSN: 0142-0615 Wydawca: ELSEVIER SCI LTD, THE BOULEVARD, LANGFORD LANE, KIDLINGTON, OXFORD OX5 1GB, OXON, ENGLAND Opublikowano: Grudzień 2012 Autorzy / Redaktorzy / Twórcy
Grupa MNiSW: Publikacja w czasopismach wymienionych w wykazie ministra MNiSzW (część A) Punkty MNiSW: 30 Klasyfikacja Web of Science: Article Pełny tekst DOI Web of Science Keywords: Relay-distribution station  Reliability  Failure frequency  Cost of unreliability  |
This paper introduces the possibility of application of u- and k-coefficient to operational reliability analysis of MV/LV transformer/distribution substations. The failure duration index was shown to have specific constraints in cost-related assessments of electric power system reliability. A direct correlation was assumed to exist between the failure duration and the actual emergency shutdown time, which can be shown with the u- and k-coefficients. The value of both indices has been determined on the basis of empirical data collected at two major power plants in Poland throughout the period of 10 years.