Attempt to improve indoor air quality in computer laboratories

Czasopismo: Procedia Engineering   Tom: 172, Zeszyt: 2017, Strony: 1154-1160
ISSN:  1877-7058
Wydawca:  ELSEVIER SCIENCE BV, SARA BURGERHARTSTRAAT 25, PO BOX 211, 1000 AE AMSTERDAM, NETHERLANDS
Opublikowano: Luty 2017
Seria wydawnicza:  Procedia Engineering
Liczba arkuszy wydawniczych:  1.00
 
  Autorzy / Redaktorzy / Twórcy
Imię i nazwisko Wydział Katedra Do oświadczenia
nr 3
Grupa
przynależności
Dyscyplina
naukowa
Procent
udziału
Liczba
punktów
do oceny pracownika
Liczba
punktów wg
kryteriów ewaluacji
Marek Telejko orcid logo WBiAKatedra Technologii i Organizacji Budownictwa *****Niespoza "N" jednostkiInżynieria lądowa, geodezja i transport10015.00.00  

Grupa MNiSW:  Materiały z konferencji międzynarodowej (zarejestrowane w Web of Science)
Punkty MNiSW: 15
Klasyfikacja Web of Science: Proceedings Paper


DOI LogoDOI     Web of Science Logo Web of Science    
Słowa kluczowe:

fizyka budowli  wentylacja  wymiana powietrza  jakość powietrza wewnętrznego 


Keywords:

building physics  ventilation  air exchange  indoor air quality 



Abstract:

Low indoor air quality (IAQ) can impact occupants' health and lead to poor productivity or low academic performance. Therefore the provision of good IAQ in classrooms and laboratories is very important. This paper presents the results of the investigation devoted to the quality of indoor air in computer laboratories of selected Polish high schools. Six schools in a town with a population of 200 000 inhabitants were involved in the investigations. The participating school buildings were built between 1975 and 1991 and had gravity ventilation systems. The variability of basic IAQ parameters, i.e., temperature, relative humidity and carbon dioxide level, was analysed and the assessment of the computer laboratories in terms of microbiological purity was performed. The outomes confirmed the low quality of the indoor air in these buildings. Certain modifications aimed at improving IAQ were proposed during the investigations. Two solutions were implemented. The first solution involved a twofold increase in the volume of supply air from 90 m(3)/h to 180 m(3)/h. The other modification consisted in installing indoor air cleaning devices based on the radiant catalytic ionization technology (RCI). The results of this study indicate that the proposed solution offers the potential to improve IAQ within computer labs. (C) 2017 Published by Elsevier Ltd.